The VRF system should work very well for all of the

               smaller classrooms, labs, offices and production

               spaces. These systems will require separate outside air

               systems to introduce conditioned fresh air to the rooms.
               These will be centralized and fresh air ducted to the

               spaces through the ceiling plenums. We recommend

               that these be tied into an energy recovery system from

               the bathroom exhausts.




               It has been noted that the existing steel bar joist roof

               members may not be large enough to support roof

               mounted HVAC equipment. There are many rooftop

               units existing, but the new equipment may be

               concentrated and thus larger than the existing. If this is

               the case, then the equipment can be mounted on the
               ground near the building, taking into account that

               screening and sound baffling may be needed as well.

               Some structural supports might also be added to

               accommodate roof mounted equipment.







                                                                                                                                  Dedicated Outdoor Air System with Energy Recovery









                                                                                                                                                                                                                              SDCA 66