Building System Specifications
Table 1. Optimized Building Performance Implementation Requirements Table
Refer to below table for detail and level of achievement recommendations for each category.
Building System Prototype Value Reference System Description
Specification
Walls R-Value ≥ 20 IECC 2012 3 inch rigid XPS
Roof R-Value ≥ 30 IECC 2009 5.5 inches of closed-cell spray foam in truss cavity
Floor R-Value ≥ 19 IECC 2012 Fiberglass-batts underneath floor, if applicable
Windows U-Value ≤ 0.3 ENERGY STAR NFRC Certified Window
SHGC ≤ 0.25 ENERGY STAR NFRC Certified Window
Air Leakage ACH50 ≤ 3 IECC 2012 Achieve continuous air barrier by sealing all wall, ceiling, and floor
penetrations to the outside
Mechanical Constant CFM 20 ASHRAE 62.2 Energy Recovery Ventilator (ERV); ducts deliver fresh air
Ventilation
Space Conditioning SEER ≥ 14.5 ENERGY STAR Ductless mini-split heat pump
HSPF ≥ 8.2 ENERGY STAR
Water Heater EF ≥ 0.90 ENERGY STAR Tankless; gas
Appliances ENERGY STAR ENERGY STAR certified, if applicable
Lighting ENERGY STAR LED; ENERGY STAR certified
Plumbing fixtures Gallons Per 0.5 WaterSense Low-flow bathroom sinks
Minute (GPM)
Gallons Per 1.5 WaterSense Low-flow kitchen sink/shower
Minute (GPM)
Gallons Per ≤ 1.28 WaterSense Dual-flush water closets